Radiant barrier sheathing panels use the same APA-rated plywood or OSB specified for standard roof sheathing. The structural panel component should meet the same performance requirements as any roof deck panel, identified through the APA trademark. For specification of the radiant barrier facing, consult the panel manufacturer's product data.
For panel design capacities, section properties, and how to read APA trademark stamps, download D510 – Panel Design Specification.
Key Selection Criteria
Standards — Substrates are manufactured to PS 1 (plywood), PS 2 (wood structural panels), or APA PRP-108 — the same standards recognized in all U.S. model building codes for conventional roof sheathing.
Panel Grades — Typically graded as APA Rated Sheathing. Structural I Rated Sheathing may be specified where enhanced cross-panel strength and racking shear resistance are required. Confirm grade availability with the panel manufacturer.
Bond Classifications — Exposure 1 is standard for roof sheathing and resists moisture effects during construction. Exterior classification is available where long-term weather exposure is anticipated.
Span Ratings — Follow standard rated sheathing conventions. The APA trademark displays two numbers (e.g., 32/16) — the left number indicates maximum center-to-center spacing of roof supports in inches. Select the rating that matches your framing layout and design loads.
Code Provisions — Structural radiant barrier panel provisions follow the same building code requirements as conventional roof sheathing. Energy code compliance for the radiant barrier component is addressed through the IECC performance path — refer to APA's The Performance Path to Energy Code Compliance, Form R505, for trade-off values by climate zone.
Mechanical Properties — Structural performance is determined by the plywood or OSB substrate. The radiant barrier facing does not alter the structural capacity of the panel.
Radiant Barrier Facing Considerations
The reflective aluminum face must be installed facing the attic air space (downward) and must face an open air gap to function properly.
Proper attic ventilation should be designed per local code requirements and manufacturer recommendations.
The radiant barrier facing should conform to ASTM C1313, Standard Specification for Sheet Radiant Barriers for Building Construction Applications.
Consult the panel manufacturer for product data sheets and installation instructions specific to the reflective facing.